Three-Phase Power Calculator

Engineering Calculators › Three-Phase Power Calculator
Engineering · Electrical

Three-Phase Power Calculator

Find the real power, current or voltage of a balanced three-phase load — and get the apparent power (kVA), reactive power (kVAR) and the line current you need for breaker and wire sizing.

Real power

Three-Phase Power, Made Practical

Three-phase power runs almost everything industrial — motors, chillers, pumps, large HVAC. This calculator answers the question you actually have: how much current will this load draw (so you can size the breaker and wire), or how much power a given voltage and current represent. Enter what you know and solve for the rest.

P = √3 × VL × IL × PF

That is real power in watts, using line-to-line voltage VL, line current IL and power factor PF. Apparent power (what the utility and your conductors actually see) drops the power factor:

S = √3 × VL × IL  (kVA)

and reactive power is Q = √(S² − P²) in kVAR. Rearranging the first equation gives the line current for sizing: IL = P / (√3 × VL × PF).

Wye vs Delta

The power formulas above use line quantities and are the same for both connections. What changes is what each phase sees. In a wye (Y) connection the phase voltage is VL / √3 and the phase current equals the line current. In a delta connection the phase voltage equals VL and the phase current is IL / √3. The calculator reports both per-phase values.

Worked Example

A 480 V load drawing 50 A at 0.85 power factor: P = 1.732 × 480 × 50 × 0.85 = about 35.3 kW, with S = 41.6 kVA. For continuous duty you would size conductors and the breaker for 50 × 1.25 = 62.5 A.

Applications

  • Motor circuits — find full-load current to size feeders and overloads.
  • HVAC & chillers — convert nameplate kW or kVA to current draw.
  • Generators & transformers — check kVA loading against rating.
  • Panel & feeder sizing — turn a load in kW into the amps your wire must carry.
  • Power factor correction — see the reactive power you are paying to move.

Frequently Asked Questions

Do I use line or phase voltage?

Use line-to-line voltage (the number on the nameplate, like 208 V, 480 V) with line current. The √3 factor already accounts for the three phases.

What if I do not know the power factor?

Motors at full load are often around 0.85–0.9; lightly loaded motors are lower. Resistive loads (heaters) are 1.0. If unsure, 0.85 is a common planning value.

Why is apparent power (kVA) larger than real power (kW)?

Power factor below 1 means current and voltage are out of phase, so conductors carry more current than the real power alone would suggest. Wire and breakers are sized to kVA / current, not kW.

Results assume a balanced three-phase system and are for education and preliminary sizing. Final conductor and overcurrent sizing must follow the applicable electrical code (for example the NEC) and account for temperature, conduit fill, derating and voltage drop.
Scroll to Top

The calculators and tools on Formula Factory are provided for general guidance and informational purposes only. Results are estimates based on standard formulas and the values you enter — they do not constitute professional engineering, electrical, or architectural advice. Always verify calculations with a qualified professional before making decisions for any safety-critical, code-compliance, or commercial application. Formula Factory makes no representations or warranties as to the accuracy or completeness of any result, and accepts no liability for errors, omissions, or any outcomes arising from reliance on this information.