Electrical boxes have a volume limit so wires are not crammed in. Each conductor counts for a set volume; add them up and the total must fit the box. This chart gives the volume per conductor.
| Wire size | Volume per conductor |
|---|---|
| 14 AWG | 2.00 cu in |
| 12 AWG | 2.25 cu in |
| 10 AWG | 2.50 cu in |
| 8 AWG | 3.00 cu in |
See the Conduit Fill Chart and How to Wire a Receptacle.