Electrical boxes have a volume limit so wires are not crammed in. Each conductor counts for a set volume; add them up and the total must fit the box. This chart gives the volume per conductor.
| Wire size | Volume per conductor |
|---|---|
| 14 AWG | 2.00 cu in |
| 12 AWG | 2.25 cu in |
| 10 AWG | 2.50 cu in |
| 8 AWG | 3.00 cu in |
FAQ
What happens if an electrical box is overfilled? Overfilling a box leaves too little room for wires to bend safely behind devices, increasing heat buildup and the risk of damaged insulation or a poor connection. Box fill calculations exist specifically to keep enough free volume for safe wire management.
See the Conduit Fill Chart and How to Wire a Receptacle.