Even lighting depends on spacing fixtures relative to their mounting height. The spacing-to-height ratio (SHR) sets the maximum gap for uniform coverage.
| Distribution | Spacing-to-height ratio |
|---|---|
| Narrow / direct | 0.5 to 1.0 |
| Medium | 1.0 to 1.5 |
| Wide / general | 1.5 to 2.0 |
| Indirect / troffer | up to 1.5 |
See the Illuminance Uniformity Calculator and the Uniformity Ratio Formula.
Spacing and mounting height
Even lighting depends on how far apart the fixtures are compared with their height above the work plane. The spacing to height ratio gives the largest spacing that keeps the light reasonably uniform. Fixtures that spread their light widely can be spaced farther apart than narrow ones, so the ratio depends on the type of distribution.
A worked example
With a 9 foot ceiling and a work plane at 2.5 feet, the mounting height is 6.5 feet. A fixture with a ratio of 1.5 can be spaced up to about 9.75 feet apart. Fixtures along a wall are usually placed closer to the wall, at about half the spacing or less, so that the wall is not left dark. Check the result with the photometric data for the fixture, and adjust for high ceilings and tasks that need more even light.