Fixture Spacing Guide

Even lighting depends on spacing fixtures relative to their mounting height. The spacing-to-height ratio (SHR) sets the maximum gap for uniform coverage.

Distribution Spacing-to-height ratio
Narrow / direct 0.5 to 1.0
Medium 1.0 to 1.5
Wide / general 1.5 to 2.0
Indirect / troffer up to 1.5
The spacing rule. Maximum spacing = SHR × (mounting height − work-plane height). Exceed it and you get dark gaps between fixtures.

See the Illuminance Uniformity Calculator and the Uniformity Ratio Formula.

Spacing and mounting height

Even lighting depends on how far apart the fixtures are compared with their height above the work plane. The spacing to height ratio gives the largest spacing that keeps the light reasonably uniform. Fixtures that spread their light widely can be spaced farther apart than narrow ones, so the ratio depends on the type of distribution.

A worked example

With a 9 foot ceiling and a work plane at 2.5 feet, the mounting height is 6.5 feet. A fixture with a ratio of 1.5 can be spaced up to about 9.75 feet apart. Fixtures along a wall are usually placed closer to the wall, at about half the spacing or less, so that the wall is not left dark. Check the result with the photometric data for the fixture, and adjust for high ceilings and tasks that need more even light.

Scroll to Top

The calculators and tools on Formula Factory are provided for general guidance and informational purposes only. Results are estimates based on standard formulas and the values you enter — they do not constitute professional engineering, electrical, or architectural advice. Always verify calculations with a qualified professional before making decisions for any safety-critical, code-compliance, or commercial application. Formula Factory makes no representations or warranties as to the accuracy or completeness of any result, and accepts no liability for errors, omissions, or any outcomes arising from reliance on this information.